3.6. Electrical Requirements - North American
North American Sure Sort units require an AC line voltage of 120/208 VAC,
single phase, 60Hz (2 Lines + Neutral + Ground to Earth).
• Line to Line voltage = 208VAC +6%/-10%
• Line to Neutral voltage = 120VAC +6%/-10%
The machine is supplied with a 15 ft. (4.57 m) length of 10/4 SO cord, and
NEMA locking plug L14-30P, connected to the AC distribution enclosure of the
Induct conveyor module.
The customer must provide a 30 Amp maximum circuit breaker-protected
circuit using a NEMA rated L14-30R locking receptacle (Hubbell HBL2713 or
equivalent). See North American plug and receptacle diagram in Figure 3-13.
NEMA L14-30 PLUG
(HUBBELL # HBL2711)
FEMALE RECEPTACLE (SITE SIDE-CUSTOMER SUPPLIED)
NEMA L14-30 RECEPTACLE
(HUBBELL # HBL2713 OR EQUIVALENT)
Figure 3-13: North American plug and receptacle requirements