10
8
.4
SETTING RANGES FOR SWITCHING OUTPUTS
Switching point function
Measuring range
In bar
0 .. 16
0 .. 40
0 .. 100
0 .. 250
0 .. 400
0 .. 600
Window function
Measuring range
In bar
0 .. 16
0 .. 40
0 .. 100
0 .. 250
0 .. 400
0 .. 600
*All ranges given in the table are adjustable by the increments shown.
9
Basic settings
In order to adapt the unit to a particular application, the function of the EDS 300 can be altered via
several basic settings. These are combined in one menu.
9.1 ALTERING THE BASIC SETTINGS
NOTE:
• When the menu is activated no switching operations are carried out.
• Switch off supply voltage or disconnect the unit from the supply voltage.
To close the basic setting menu:
Call up the menu point "END", set to "YES", the EDS 300 returns to the normal display mode after
2 seconds.
NOTE:
• If after about 50 seconds no keys have been pressed, the menu automatically closes
down. Any changes which may have been made will not be saved
Status: 19.09.2018
Switch point
In bar
0.3 .. 16
0.6 .. 40
1.5 .. 100
3.0 .. 250
6.0 .. 400
15.0 .. 600
Lower switch value
In bar
0.2 .. 15.9
0.4 .. 39.8
1.0 .. 99.5
2.0 .. 249.0
4.0 .. 398.0
10.0 .. 595.0
(for summary see 8.2)
HYDAC ELECTRONIC GMBH
Hysteresis
In bar
0.1 .. 15.8
0.2 .. 39.6
0.5 .. 99.0
1.0 .. 248
2.0 .. 396
5.0 .. 590
Upper switch value
In bar
0.3 .. 16
0.6 .. 40
1.5 .. 100
3.0 .. 250
6.0 .. 400
15.0 .. 600
EDS 300
Increment*
In bar
0.1
0.2
0.5
1.0
2.0
5.0
Increment*
In bar
0.1
0.2
0.5
1.0
2.0
5.0
Part No.: 669648 E