Additional pairs of photocells can be installed at any time on a system for swing gates.
Up to a maximum of 6 pairs of photocells with safety functions can be added (as shown in the example A-B-C-D-E-F in fig. 54) and 1 pair with
a control function (as shown in the example G in fig. 54) which performs an Opening manoeuvre only.
For the correct location of these pairs of photocells, refer to fig. 54.
In order for the control unit to recognise each pair of photocells and the specifically assigned function, the devices must be assigned with
addresses by the insertion of one or two electric jumpers (Table 3) or no jumper at all (Table 3). In this way when the control unit receives the
input from the photocells it will activate the motor for the corresponding manoeuvre.
The address assignment procedure is performed both on the TX and RX photocell as follows:
For photocells "A-B-C-D-E-F"
Take care to observe the following warnings:
• the electric jumpers must be positioned on the two photocells using the same configuration;
• the same configuration used on one pair of photocells must NOT be used on other photocells.
To program these pairs of photocells (if fitted on the system) proceed as follows:
01. Open the cover of the photocell.
02. In fig. 54 locate the position in which the specific photocells are installed.
03. In Table 3 select the required configuration and insert electric jumpers in the two photocells.
For photocells "G"
Take care to observe the following warnings:
• These photocells have a different function from the other (controlling the automation), and therefore must be positioned at a specific distance
to avoid possible interference.
• These photocells remain powered also when the automation is on standby and in the event of a power failure, if the buffer battery is fitted,
this will reduce the standard lifetime (see paragraph 6.6).
To program these pairs of photocells (if fitted on the system) no electric jumper must be inserted (see Table 3).
54
Pair of photocells
A
Photocells h = 50 cm
(these are activated when
the gate is in the Closing phase)
B
Photocells h = 100 cm
(these are activated when
the gate is in the Closing phase)
C
Photocells h = 50 cm
(these are activated when the gate
is in the Opening or Closing Phase)
D
Photocells h = 100 cm
(these are activated when the gate
is in the Opening or closing Phase)
18 – English
SELECTING OPERATING MODES OF PHOTOCELL PAIRS
TABLE 3
Electric jumpers
Pair of photocells
E
Photocell to right
(these are activated when the gate
is in the Opening phase)
F
Photocell to left
(these are activated when
the gate is in the Opening phase)
G
Photocell with
Gate opening only
command
Electric jumpersi