13
Technical data
13.1
Dimensions
Fig. 145: Dimensions
A
Side view
B
Bottom view (cable entries)
13.2
Base analogue inputs
13.2.1
Temperature measurement 1 (IN4)
Probe / signal type
Pt100 DIN EN 60751
Pt1000 DIN EN 60751
Resistance
thermometers with
customer-specific
characteristic line (
to 400 Ω to 4000 Ω
Sensor line resistance
Conductance
compensation
1
(
) MB: Measuring range
(
2
) With the help of custom linearisation, a sensor characteristic can be entered
3
(
) R
: Maximum resistance value of the measuring range (400 Ω or 4000 Ω)
Max.
Type of
Type of
connection
connection
2-wire / 3-wire
-200 to +850 °C ≤ 0,05 % of the
2-wire / 3-wire
-200 to +850 °C ≤ 0.1% of the MB (
2-wire / 3-wire
0 to 400Ω
2-wire / 3-wire
0 to 4000Ω
2
)
Maximum of 30 Ω per lead for 3-wire connection
Not required in a 3-wire connection. With a 2-wire circuit, you can balance the lines
for each input by adjusting the actual value under the "offset" setting.
C
Front view
Measurement
accuracy
=0,1% of R
Max.
c≤0.1% of R
Max.
243
Technical data
Ambient
temperature error
= 50 ppm / K
MB (1
)
1
= 50 ppm / K
)
≤ 100 ppm / K≤
100 ppm / K
(
3
)