Versatronic cooling water
This table only applies to Ci or Cr measurements in the cooling water configuration (see
Ä Chapter 5.3 'Material code' on page 40)
Configuration
point
KT X designation
KT X W-
KT X hyst. W +
KT X hyst. Ws
Configuration point Selection / option
KT X biocide dos.
duration 1
KT X biocide dos.
duration 2
(only with C1)*
KT X exposure
KT X time precirculation Hours / minutes / seconds
Ä Chapter 5.3 'Material code' on page 40
* = see
Selection / option
Text box
Number field
Range: - 99999-99999
Number field
Range: - 99999-99999
Number field
Range: - 99999-99999
Hours / minutes / seconds
(hh:mm:ss) Range: 0-23: 0-59:
0-59
Hours / minutes / seconds
(hh:mm:ss) Range: 0-23: 0-59:
0-59
Hours / minutes / seconds
(hh:mm:ss) Range: 0-23: 0-59:
0-59
(hh:mm:ss) Range: 0-23: 0-59:
0-59
141
Explanation
Channel. Edit X name
Choosing the lower switching point
W-
(Underflow of W = desalination off)
Choice of the upper switching point
W + as a positive hysteresis of W-
(W + W + = hysteresis + W)
(Excess of W + = desalination on)
Select the switching point for the
pre-desalination Ws as a positive
hysteresis of W-
(W + hysteresis Ws = Ws)
(Excess of Ws + Dosage time
points, biocide = predesalination
on)
Explanation
Determining the dosing time for
biocide 1 dosing
Determining the dosing time for
biocide 2 dosing
Set the exposure time
(Time the desalination remains
locked for which after completion of
the biocide.)
Set the precirculation time
(How long the circulation should run
after the circulation pump is
activated and before the biocide
dosing is enabled.)
417102269 Rev. 2-08.2020
Device menu
Default
Name
1600 µS/cm
200 µS/cm
(W+ = 1800 µS/cm)
100 S / cm
(Ws = 1700 S / cm)
Default
00:00:10
00:00:10
00:00:10
00:00:10