Items in the Basic
The Basic menu contains the following items:
Menu
MPP Tracker 1
-
-
-
USB logbook
SMS / Relay
-
-
Ground Settings
-
-
Insulation settings
-
-
-
40
DC operating mode:
MPP AUTO
FIX
MPP USER
Fixed voltage:
For entering the fixed voltage, 120–440 V
MPPT1 initial voltage:
For entering the MPPT1 initial voltage, 120–440 V
Activating or deactivating the function to save all error messages to a USB stick
AUTO / OFF / ON
Event delay:
For entering the delay time from when an SMS is sent or from when the relay should
switch
900–86400 seconds
Event meter:
For entering the number of errors following which an SMS is sent or the relay should
switch:
10–255
Ground mode:
Off / Positive / Negative
Ground monitoring
(only displayed if the ground mode is set to Positive or Negative):
Warn Err / Error / Warning
(only displayed if the ground mode is set to Negative or Off)
Insulation warning:
to activate and deactivate the insulation monitoring with display of a warning without
interrupting feed-in in the event of an insulation error
ON / OFF (depends on the country setup)
Threshold warning:
to set an insulation threshold below which the inverter displays a warning (without
interrupting feed-in)
0–1000 kOhm (depends on the country setup set)
Threshold error:
to set an insulation threshold under which the inverter displays an error message
and interrupts feed-in
0–1000 kOhm (depends on the country setup)