7.1.6 VER
Software version
The installed software version is displayed (5-digit number with abbreviation VCO)�
7.1.7 AO3
Analogue Offset (for analogue output 3)
Current value displayed and provided for an input value of 0 Hz/RPM�
Value range
Default value
7.2 Application parameters
7.2.1 SPx
Switch Point (outputs 1/2)
Value at which the output 1/2 changes its switching state according to switching function
FOx�
Values
Default value
7.2.2 HYx
Hysteresis (for switch points SP1/SP2)
The hysteresis value determines the distance between the switch-off point and the switch
point SPx� Prevents a possible chattering of the switching output� In connection with the
switching functions 5 and 6 (FOx) an acceptable range or an error range can be defined�
Values
Default value
7.2.3 STx
Start-Up Delay Time (for outputs 1/2)
Enables the suppression of error messages when a plant is started� When the device is
switched on or when the 24 V signal is removed from the reset input, the respective output
for the time set here is in the "good" state (= no fault)�
Values
Notice de montage et d'exploitation – Entraînements pour élévateurs à godets – Série X..e
0�0���20 mA (typical setting: 0�0 or 4�0 mA)
4�0 mA
0�1 ��� 1000�0 Hz or 1 ��� 60000 RPM (unit depends on DIM)
SP1 = 100 RPM, SP2 = 1000 RPM
0�0���1000�0 % of the value for SPx
5�0
0�0���1000�0 s