ENGLISH
9.2.4 User menu
Access the drop-down menu
the following items:
1. Working mode.
2. Holiday mode setting.
3. Alarm panel.
1. Working mode
Work modes
Unit state
Current gear
Holiday mode
Schedules
Summer / Winter mode
Temperature of comfort
From this screen you can:
• Switch the appliance on or off
• Change speed.
• Activate or deactivate Holiday mode.
• Enable or disable Hourly Programming.
• Set Summer / Winter mode.
> SUMMER / WINTER mode
Under "Summer/Winter Mode" there is a sub-menu from which you can select the working mode (Auto, Winter, Summer, Ventilation)
and the set temperature values for activating the winter or summer mode and the comfort temperature, which is the temperature
against which the unit activates/deactivates the bypass.
Summer / Winter mode
Winter mode activation
Summer mode activation histeresis
Work mode
Temperatura di comfort
• Working mode: Auto
The appliance automatically sets the winter or summer mode:
- WINTER MODE
• When the intake temperature (Inlet/Fresh Air) falls below the value of the winter mode activation temperature, the pre-heater is
enabled.
• The bypass function is never active in winter mode.
- SUMMER MODE
• When the intake temperature rises above the summer mode activation hysteresis, the pre-heater is switched off and automatic
bypass operation is enabled. The opening of the valve allows direct extraction of indoor air (B - fig.2), preventing passage inside
the heat exchanger. Instead, the flow of air (C - fig.2) going into the dwelling continues to pass through the heat exchanger, which
will no longer be effective.
Note 1: In order to facilitate closing and opening of the bypass valve, the motors reduce the speed to 20% (or to the minimum value, if
greater than 20%) for a period of 180 seconds. When the appliance is switched on, the bypass damper closes again for 180 seconds.
54
from the "
Device parameters" button to access the "User Menu" and its sub-menu made up of
On
MIN
Off
No
23°C
8°C
6°C
-20°C
14°C
0°C
23°C
8°C
20°C
20°C
30°C