Utilizzo dell'UPS KEOR XPE
S8
INVERTER MASTER SYNCHRONIZED
The inverter is synchronised with the MASTER.
This status is present only on the SLAVE Power Unit and indicates the
inverter is synchronised with the signal sent from the MASTER.
S13
BATTERY CHARGE
The battery is charging.
The static switch of the battery is closed and the battery is charging.
S14
BATTERY CHARGE I
The battery is charging.
The static switch of the battery is closed and the battery is in the first I/U
charging phase (DIN 41773), with constant current and increasing
voltage.
S15
BATTERY CHARGE U
The cyclic charge of the battery is enabled.
The static switch of the battery is closed and the battery is in the second
and final I/Ucharging phase (DIN 41773), with voltage current and
decreasing current.
S16
HIGH BYPASS COMMUTATION
Switching with bypass high voltage.
Switching from inverter to bypass with inverter switch off caused by
bypass voltage over or equal to 10% of the bypass rated voltage.
S23
RTC
Clock faulty on Power Unit.
Power Unit clock is not working properly.
S24
GREEN CONVERSION
Power Unit operating status.
The Power Unit is in the GREEN CONVERSION operating status.