Alarm
A45
Description
High temperature of the heat sink on the static switch.
Possible
Fault of the heat sink cooling fans.
causes
The room temperature or cooling air temperature is too high.
Solutions
2. Check the fans operation.
3. Clean the ventilation grids and the air filters, if any.
4. Check the air conditioning system (if present).
5. If the alarm persists, contact our technical support service.
Alarm
A46
Description
The load connected to the system has reached such a level there is no
longer redundancy in the event of a fault or malfunction of a Power Unit.
Continuity is not guaranteed in the event of a fault on one of the Power
Units.
Possible
The total load is higher than the maximum expected value.
causes
Possible failure on the measuring circuit.
Solutions
1. Check the load fed by the system.
2. If the alarm persists, contact our technical support service.
Alarm
A47
Description
The battery limitation current over the limits.
Possible
The Power Unit detected the battery limitation current out of limits
causes
Solutions
1. Check the battery current sensor.
2. Check the battery locks.
3. If the alarm persists, contact our technical support service.
Alarm
A50
Description
The inverter current sensor has detected a peak of the current and the
control inverter is in limitation.
Possible
Load problem.
causes
Measuring circuit failure.
Solutions
1. Check the loads connected to the Power Unit output.
2. If the alarm persists, contact our technical support service.
KEOR XPE UPS user manual
Utilizzo dell'UPS KEOR XPE
HIGH TEMPERATURE SSW
LOST OF REDUNDANCY
PEAK BATTERY OVERCURRENT
and switch off the inverter, booster and disconnected the battery
from the Power Unit.
CURRENT INVERTER SATURATED