5.3.2 Battery test
The BATTERY TEST section allows you to run a short battery discharge test. If the battery is
not sufficient, at the end of the test, the "AS10 BATTERY FAULTY" alarm will be generated.
If configuration of the battery is distributed, this section will be disabled, but it will be present in
the controls of the individual Power Units.
Possible power loss
This test can be risky for the continuity of the changes, if the battery is not completely
charged.
5.3.3 Reset alarms log
To delete the events log, select the RESET LOG section and confirm the operation on the next
screen.
Confirming this operation deletes the alarms log of the entire system (IOBM and Power Unit).
Data loss
The events log contains a lot of very important data to monitor the behaviour of the
device over time. You are advised to save the data before deleting it.
48
OMAF9213 REV. C
KEOR XPE UPS user manual
Manuel de l'utilisateur de l'ASI KEOR XPE