Télécharger Imprimer la page

LEGRAND KEOR XPE Serie Manuel De L'utilisateur page 86

Masquer les pouces Voir aussi pour KEOR XPE Serie:

Publicité

Les langues disponibles

Les langues disponibles

Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
86
OMAF9213 REV. C
KEOR XPE UPS user manual
Manuel de l'utilisateur de l'ASI KEOR XPE
Utilizzo dell'UPS KEOR XPE
AS35
DIESEL MODE
The system is supplied by the diesel generator.
or
At least one Power Unit has enabled alarm A35 DIESEL MODE.
 The auxiliary contact which activates the diesel generator
connected to the the IOBM is closed, and imposes this operating
mode.
 Refer to alarm A35 DIESEL MODE of the Power Unit.
1. Wait for the diesel generator to stop as soon as mains voltage is
restored.
2. Check the auxiliary contact connection of the start signal on the
diesel generator to the auxiliary terminals of the IOBM.
3. Refer to alarm A35 DIESEL MODE of the Power Unit.
4. If the alarm persists, contact our technical support service.
AS36
DC FASTSHUTDOWN
At least one Power Unit has enabled alarm A36 DC FASTSHUTDOWN.
 Refer to alarm A36 DC FASTSHUTDOWN of the Power Unit.
1. Refer to alarm A36 DC FASTSHUTDOWN of the Power Unit.
AS37
OCBD OPEN
At least one Power Unit has enabled alarm A37 OCBD OPEN.
 Refer to alarm A37 OCBD OPEN of the Power Unit.
1. Refer to alarm A37 OCBD OPEN of the Power Unit.
AS38
INVERTER --> LOAD
At least one Power Unit has enabled alarm
A38 INVERTER --> LOAD. Alarm on in "ECO" mode.
 Refer to alarm A38 INVERTER --> LOAD of the Power Unit.
1. Refer to alarm A38 INVERTER --> LOAD of the Power Unit.

Publicité

loading