Manuel de l'utilisateur de l'ASI KEOR XPE
Alarm
A56
Description
The rectifier input voltage is unbalanced.
Possible
The voltages of the rectifier input are unbalanced.
causes
Defect of the measuring circuit.
Solutions
1. Contact the technical support service.
Alarm
A60
Description
The output voltage sensor has detected a variation of the voltage over
or under the limits.
Possible
Output voltage feedback problem.
causes
Solutions
1. If the alarm persists, contact our technical support service.
Alarm
A61
Description
The Power Unit has stopped due to the operation of the protection
sensor as a result of high sudden DC voltage variations over the limits.
Possible
DC bus voltage problem.
causes
Solutions
1. Check that there aren't short circuit in DC bus.
2. Verify the status of the Power Unit.
3. Verify the battery blocks.
4. Verify the DC voltage value.
5. If the alarm persists, contact our technical support service.
Alarm
A62
Description
Sudden increase of the AC input voltage (fast sensor)
Possible
Voltage spike on the AC mains.
causes
Possible internal fault.
Solutions
1. Check the mains voltage.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A63
Description
During the Power Unit start-up a failure prevented the proper execution
of the sequence.
Possible
Control devices in wrong position or operated improperly.
causes
Possible internal fault.
Solutions
1. Make sure the position of the control devices (isolators, selectors)
2. If the alarm persists, contact our technical support service.
KEOR XPE UPS user manual
Utilizzo dell'UPS KEOR XPE
MAINS UNBALANCED
OUTPUT VOLTAGE FAILURE
MAX DC VOLTAGE
MAINS OVERVOLTAGE
STARTING SEQUENCE BLOCKED
is as specified in the procedures (see "Installation and start-up"
section).
OMAF9213 REV. C
107