3.4
OPERATING STATUS
The UPS has five different operating modes, as described below:
 Normal operation
 Green Conversion
 Bypass operation
 Battery operation
 Manual bypass
3.4.1 Normal operation
During normal operation all the circuit breakers/isolators are closed, except for MBCB
(maintenance bypass).
The rectifier is supplied by the AC three-phase input voltage which, on its turn, feeds the
inverter and compensates mains voltage as well as load variations, keeping the DC voltage
constant. At the same time, it provides to charge the battery. The inverter converts the DC
voltage into an AC sine-wave with stabilized voltage and frequency, and also supplies the load
via its static switch SSI.
Picture 2 – Normal operation centralized battery
KEOR XPE UPS user manual
Manuel de l'utilisateur de l'ASI KEOR XPE
Utilizzo dell'UPS KEOR XPE
OMAF9213 REV. C
21