Télécharger Imprimer la page

Webasto Next Notice De Montage page 27

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 116
energy management system). A CAT 7 network cable is
recommended. The LAN cable must be passed through
the left-hand opening in the wall box in order to connect
it to the LAN socket.
Active power increase
4.6
Fig. 5
The active power control as per the rules of VDE
AR-4100 should be connected as follows:
The two cables from the ripple control receiver or the
floating contact must be connected to this connector in
positions 3 and 4 (see Fig. 5). The two cables can be as-
signed to pos. 3 and 4 in any order (sequence). (max.
cable cross section 1.5 mm²).
WARNING
No voltage should be applied between terminals 3
and 4.
4.7
DIP switch settings
DANGER
High voltages.
Danger of fatal electric shock.
u
u
Ensure safe isolation from the power supply.
DIP switches determine the maximum current. The cur-
rent can be adjusted in 1 A increments using the Charger
Setup app up to the maximum value that is configured by
the DIP switches.
Fig. 6
DIP switch left/ON = 1
DIP switch right/OFF = 0
DIP-switch factory setting:
D1
D2
D3
D4
Off
Off
Off
On
5111233C_ISI_Next
NOTE
Changes to the DIP switch settings become active
after restarting the charging station.
D1
D2
D3
[A]
0
0
0
32
0
0
1
10
1
0
0
13
1
0
1
16
0
1
0
20
0
1
1
25
1
1
0
8
1
1
1
0
WARNING
The DIP switches must be adapted to the upstream in-
stallation by a qualified electrician prior to initial oper-
ation.
D4 0= no unbalance load limit for single-phase char-
ging.
1= unbalance load limit at 16 A and D1-D3 > 20 A
(for CH and AT).
D5 0= no unbalance load limit for single-phase char-
ging.
1= unbalance load limit at 20 A and D1-D3 > 25 A
(for D).
D6 1= TN/TT system.
D5
D6
0= IT system (only single-phase connection pos-
On
On
sible).
WARNING
Only a qualified electrician may adjust the settings in
the Webasto Charger Setup app.
Initial start-up
4.8
Safety check
4.8.1
Document the results of the checks and measurements
Description
carried out during initial start-up corresponding to the
Factory settings
applicable installation requirements and standards.
The Webasto Charger Setup app supports you with
checks during initial start-up.
The local regulations relating to operation, installation
and environmental protection also apply.
4.8.2
Start-up procedure
1. Remove material residues from the connection area.
2. Check that every screw is correctly tightened and
every clamp is correctly engaged.
Demo mode: charging not
3. Fit the lower cover.
possible
4. Secure the bottom cover with the mounting screws;
carefully tighten the mounting screws to the stop.
See Fig. 1.
5. Switch on power supply.
– Start sequence is activated (duration up to 60
seconds).
– White chase light running up and down. See Fig. 7,
operating status N2.
Fig. 7
1. Check initial start-up and record the measured values
in the test log. The Webasto Charger Setup app can
support you in carrying out and documenting this. An
EV simulator is used for the measurement at the
charging coupling.
2. Simulate and test the individual operating and pro-
tection functions with the EV simulator.
3. Connect the charging cable to the vehicle.
– The LED changes from green (N3) to pulsing blue
(N4), see Fig. 7.
Assembly
5
Fig. 8
Fig. 9
1 Hole for cable to building wiring system
2 Hole for LAN cable
EN