4.
Digital display
After switching on the supply voltage, the unit briefly displays "EdS" and then
displays the actual pressure (basic setting).
E
in the basic settings, the display can be altered as follows:
display of the maximum value "TOP"
this is the largest value measured in the system since the unit was
switched on or was last re-set.
display of the pre-set switching point "S.P. 1", "S.P. 2"
depending on the model, switching point 1 or switching point 2
can be permanently displayed.
display off "OFF"
the display is switched off.
depending on the setting "TOP", "S.P. 1", "S.P. 2" or "OFF" appears briefly
in the display following the switch-on message. the actual pressure can be
displayed briefly by pressing the or the key.
in the setting "display of the actual pressure", it is possible to display the
maximum value by pressing the or the key. this is displayed for 3 s.
The maximum value can be re-set in each display mode by briefly pressing
the and the keys simultaneously. this procedure is acknowledged by
the message "rES" in the display .
notes:
if the actual pressure exceeds the nominal pressure of the unit, it can no
longer be displayed and the display begins to flash.
if the actual pressure is below 0.75 % of the nominal range,
then 0 is displayed.
34
5.
Output function
5.1. switcHing outputs
the eds 3000 has 1 or 2 switching outputs. the following switching settings
can be made under basic settings:
5.1.1. switching point setting (sp)
one switching point and one hysteresis can be set for each switching output.
the respective output switches when the pre-set switching point is reached and
switches back when the pressure falls below the switch-back point.
the switch-back point is determined by the pre-set hysteresis
(switch-back point = switching point minus hysteresis).
abbreviations:
"S.P.1", "S.P.2"
"H.Y.1", "H.Y.2"
5.1.2. window function setting (win)
the window function enables a range to be monitored. for each switching output,
an upper and a lower switching value can be input which determine the range.
the respective output switches when the pressure enters this range.
upon leaving the range, i.e. when the switch-back value has been reached, the
output switches back. the lower switch-back value is just below the lower switching
value (lower switching value minus three times the increment, see point 5.4). the
upper switch-back value is just above the upper switching value (upper switching
value plus three times the increment, see point 5.4). the area between switching
value and switch-back value forms a safety zone which prevents unwanted
switching operations from occurring (e.g. triggered by pulsations from a pump).
example for switching output 1 (normally open function):
P
Off
hi.1 plus 1% FS
Safety zone
hi.1
On
Lo.1
Safety zone
Lo.1 minus 1% FS
On
Off
abbreviations:
"hi.1", "hi.2"
= High level 1 or 2
"Lo.1", "Lo.2"
= Low level 1 or 2
FS (Full Scale)
= relative to the full measuring range
note:
the window function only operates correctly (switching on and off),
when all switching values (including the safety zone) are greater
than 0 bar and lower than the nominal pressure range.
= switching point 1 or 2
= hysteresis 1 or 2
Switch-back value
Switching value
On
Switching value
Switch-back value
Off
t
= upper switching value 1 or 2
= lower switching value 1 or 2
E
35