9 Fault elimination
Characteristics/details
Connection to the visualization
cannot be established.
Incorrect display of visualization
in the web browser.
Table 18: Web browser
Characteristics/details
Measured voltage
▪ No measured value available.
Measured voltage
▪ Measured value too low
Measured voltage
▪ Measured value fluctuates
Measured current
▪ No measured value
Measured current
▪ Measured value too high
▪ Measured value too low
Table 19: Incorrect measured values
Maschinenfabrik Reinhausen GmbH 2022
Web browser
Cause
Connection cable defective.
SSL encryption active.
PC not in same subnet as visual-
ization.
Access to the visualization using
a web browser after a software
update.
9.4 Incorrect measured values
Cause
Connection has no contact in the
plug terminal.
Insulation trapped.
Wire is not inserted far enough.
Miniature circuit breaker has
tripped.
Connection faulty.
Voltage drop on the measuring
line.
Possible sources of interference:
▪ Cables laid in parallel.
▪ Tap-change operations.
Line to the current transformer in-
terrupted.
Short-circuiting jumper in current
transformer is not removed.
Current transformer not correctly
parameterized.
8741483/02 EN
Remedy
Check connection cable.
Accept SSL certificate in browser.
Call up IP address using https://.
Deactivate SSL encryption.
Check the setting of IP addresses of the device
and PC and correct if necessary.
Delete the web browser's cache.
Remedy
Check the wiring and plug terminal.
Check the fuse.
Check wiring.
Connect as shown in the connection diagram.
Check the measured voltage.
Check the measured voltage.
Increase the distance from the source of inter-
ference.
Install a filter if necessary.
Check wiring.
Remove the short-circuiting jumper.
Correct parameterization.
TAPCON
®
250
83