Cable
Power supply (external)
Voltage measurement
Current measurement
Digital signal inputs
110 V AC
Digital signal inputs
24V DC
Auxiliary voltage output
24V DC
Digital signal outputs
Analog signal inputs
Analog signal outputs
RS232, D-SUB 9-pole
RS485
CAN bus
Ethernet RJ45
Ethernet FO
RJ45 patch cables
Ground connection
Table 12: Recommendation for connection cables
®
64
TAPCON
250
Excessive line capacitance can prevent the relay contacts from interrupting
the contact current. In control circuits operated with alternating current, take
into account the effect of the line capacitance of long control cables on the
function of the relay contacts.
If you want to route Ethernet connections from a control cabinet or building,
we recommend using fiber-optic cables (in accordance with the
IEC 61850-90-4 recommendation).
Interface
Cable type
X9
Unshielded
UI-X7
Shielded
UI-X7
Unshielded
DI 8
Shielded
DI 8
Shielded
DI 8
Shielded
DO 8
Shielded
AI 4
Shielded
AO 4
Shielded
X3
Shielded
X5
Shielded
COM-X6
Shielded
COM-X6
Min. CAT5, shielded
COM X4
Duplex LC multi-
mode, Om3, 1310 nm
Min. CAT5, shielded
PE terminal
Unshielded
6.4.2 Electromagnetic compatibility
The device has been developed in accordance with applicable EMC stan-
dards. The following points must be noted in order to maintain the EMC
standards.
Conductor cross-sec-
tion
2.5 mm²
2.5 mm²
4 mm²
1.5 mm²
1.5 mm²
1.5 mm²
1.5 mm²
1 mm²
1 mm²
0.25 mm²
0.25 mm²
0.75 mm²
S/FTP
S/FTP
6 mm²
8741483/02 EN
6 Mounting
Max. length
400 m (<25 Ω/km)
400 m (<25 Ω/km)
400 m (<25 Ω/km)
400 m (<25 Ω/km)
400 m (<25 Ω/km)
25 m
140 m
2000 m (total CAN bus)
100 m
2000 m
approx. 30 cm
Maschinenfabrik Reinhausen GmbH 2022