6 Mounting
6.4.5.1 Serial interface RS485
6.4.5.2 Serial interface RS232
6.4.5.3 Ethernet interface
Maschinenfabrik Reinhausen GmbH 2022
Data cable
The device is connected via the RS485 interface (COM2) via the CPU as-
sembly module (X4) or PCB connector (see Technical data).
1. Connect the RS485 interface COM-X1 on the interface module and the in-
terface CPU-X4 together using the patch cable.
2. Connect the wires of the shielded cable in accordance with the connection
diagram.
3. Position the cable shielding, screw it into the shield clamp provided, and
provide strain relief (using a cable tie).
Data cable
The device is connected via the RS232 interface (COM2) via the CPU as-
sembly module (X5) or PCB connector (see Technical data [►Section 11,
Page 86]).
1. Connect the RS232 interface COM-X1 on the interface module and the in-
terface CPU-X5 together using the patch cable.
2. Connect the wires of the shielded cable in accordance with the connection
diagram.
3. Position the cable shielding, screw it into the shield clamp provided, and
provide strain relief (using a cable tie).
► Connect Ethernet cable (RJ45 plug) to the interface CI-X1.
6.4.6 Wiring voltage measurement/current measurement UI
You must fuse the voltage measurement circuit in accordance with the con-
ductor cross section used. You can use the following fuse types:
Standard
Rated voltage
Rated current
8741483/02 EN
Miniature circuit breaker
IEC 60947-2
110/230 V (L-N)
1.6 mA...16 A
Safety fuse
IEC 60269
®
TAPCON
250
69