11 Technical data
11.2.12 Voltage measurement U 3
Maschinenfabrik Reinhausen GmbH 2022
Measurement
Voltage inputs
Nominal voltage U
(AC)
N
U
typical (AC)
N
Max. measured voltage
Measuring accuracy
Frequency measurement
Table 57: U 3 assemblies technical data
Interface
4
3
2
1
Table 58: Connector X1
Interface
10
9
8
7
6
5
4
3
2
1
Table 59: Connector X2
8741483/02 EN
U 3
3-phase
4 (electrically isolated)
10...250 V
110 V, 110 V/√3, 230 V
150% U
when U
≤ 110 V
N
N
110% U
when U
≤ 250 V
N
N
Deviation < ±0.3% · U
N
f
: 16.7, 50 or 60 Hz
N
Measuring range: f
±15%
N
Pin
Description
4
Common reference output 1
3
Common reference output 0
2
Digital output 1
1
Digital output 0
Pin
Description
10
Not used
9
Voltage input phase 1
8
Voltage input neutral conductor 1
7
Voltage input phase 2
6
Voltage input neutral conductor 3
5
Voltage input phase 3
4
Voltage input neutral conductor 3
3
Not used
2
Voltage input phase 4
1
Voltage input neutral conductor 4
®
TAPCON
250
105