10
Technical data
10.1
General Information
Reference conditions
Sensor system
Admissible load changes
Position
Mounting position
Calibration position
Zero point correction
Display
Alignment
Size
Color
Switching status display
Measuring unit
Operation
On the device
Setup interface
10.2
Measuring range and accuracy
Nominal measuring range
0 bar to 160 bar relative pressure
0 bar to 600 bar relative pressure
a
Linearity according to limit point setting.
b
Reference conditions EN 61298-1.
c
All pressure transmitters are vacuum proof.
d
Includes: linearity, hysteresis, repeatability, deviation of measuring range initial value, and measuring range end
value
e
Includes: linearity, hysteresis, repeatability, deviation of measuring range initial value, and measuring range end
value, thermal effect on measuring range start and measuring span
f
MSP = Measuring span
DIN 16086 and DIN EN 60770
Thin-film technology
> 10 million
Any
Device upright, process connection at the bottom
Possible on-site or through setup (20% of nominal measuring range)
Positively-lit display
Display rotatable by 180° with software
Case rotatable by ±160° (use supplied combined tool)
Display 16 mm x 26 mm, font size 7 mm, 2x 4-digit
Amber since version 240.01.05
K1, K2
bar, kPa, MPa, psi, %
With the control element beneath the sealing screw with combination tool or
screwdriver 0.5 x 3 or size 2 Allen key
Pin 5 of the M12 x 1 round plug
a
Linearity
Accuracy at
d
20 °C
-
20 °C to +75 °C
e
f
% MSP
% MSP % MSP
0.1
0.25
0.5
0.1
0.25
0.5
10 Technical data
Long-term
Overload ca-
b
c
stability
pability
% MSP per
bar
year
≤ 0.2
320
900
Burst
pressure
bar
800
1800
39