6.4

Parameter

6.4.1

Input

Parameter
Unit of pressure
Offset
(zero point correction)
Damping
(filter time constant)
a
The default setting is highlighted in bold.
6.4.2

Analog output

Parameter
Type of signal
(only with analog output)
Scaling start
(only with analog output)
Scaling end
(only with analog output)
Signal in case of error
(only for analog output)
a
The default setting is highlighted in bold.
Display
Setting range
bar
MPa
psi
(%, see chapter 7.16 "Setting the digital indicator
(D.Uni)", page 34)
±20% of the measuring range
Note:
Automatic offset correction, see
chapter 7.5 "Setting the zero point (offset) (Off.P)",
page 25
0.00 to 99.99 s
Attenuation affects the behavior of the display's
analog output, and the switching outputs.
Display
Setting range
4 to 20 mA
0 bis 20 mA
0 to 10 V
0.00 to 75.00% of the nominal measuring range
25.00 to 100% of the nominal measuring range
3.4 mA or 22 mA
for output signals 4 to 20 mA
0 mA or 22 mA
for output signals 0 to 20 mA
0 V or 10.7 V
for output signals 0 to 10 V
chapter 7.9 "Setting the error signal (S.Err)",
page 29
Note:
Depending on the configured output signal
6 Operation
a
a
17