7.4.3 complete the installation of the 8036
Wire the device (see chap. 7.6) and supply power to the device.
Set the K-factor or determine it through a Teach-In procedure
(see chap. 8.8.8).
7.5
installation of a flow transmitter
SE36 with sensor-fitting S070 or
S077 in a pipe
Danger
risk of injury due to high pressure in the installation.
▶ Stop the circulation of fluid, cut off the pressure and drain the
pipe before loosening the process connections.
risk of injury due to the nature of the fluid.
▶ Respect the prevailing regulations on accident prevention and
safety relating to the use of aggressive fluids.
Follow the next steps to install the flow transmitter SE36 properly on
the sensor-fitting S070 or S077, mounted in the pipe:
7.5.1 install the sensor-fitting S070 or S077
in a pipe
Select a sensor-fitting S070 or S077 adapted to the fluid
viscosity.
19
English
Type 8026 - 8036 - SE36
Installation and wiring
To select a fitting, please refer to the chart in the technical
data sheet of the related fitting.
Install the sensor-fitting S070 or S077 in the pipe so that the
oval gear axes are in the horizontal plane (see Fig. 9).
Fig. 9: 
The oval gear axes must be horizontal (seen from the front)The 
oval gear axes must be horizontal
Correct