Total current is too high
Every output is supplied with a continuous current of max. 0.5 A.
Current loads over 0.5 A per output can lead to limited system
functioning.
O
Make sure that the current load of 0.5 A per output is not
exceeded.

6.3.6 Connecting the output module load supply

Each output module has its own M12 connection for the load
supply. Each of the 4 outputs are supplied via the load supply.
The U
and U
voltages are galvanically isolated.
Q1
Q2
The connection cable for the output module load supply must
meet the following requirements:
W
Cable socket: M12x1, 4-pin, A-coded without center hole
(to ensure correct plug-in connection)
W
Cable cross section: > 0.5 mm
W
Length: Max. 20 m
1. Set up the correct pin assignments (see Table 11) on the
plug connections if you do not use pre-assembled wiring.
2. Connect the load supply using the M12 plug.
NOTICE
2
per wire
99