AVENTICS | PROFINET-IO | R412015162–BDL–001–AE
Table 14:
Output assignment for 8x output module, 8DO_M12,
M12x1 socket
Pin
Signal
1
NC
2
O1, O3, O5 or O7
3
GND
4
O0, O2, O4 or O6
5
NC
Housing
Total current is too high
Every output is supplied with a continuous current of max. 0.5 A.
Current loads over 0.5 A per output can damage the system.
O
Make sure that the current load of 0.5 A per output is not
exceeded.
5.3.7
Connecting the output module load supply
Each output module has its own M12 connection for the load
supply. Each of the 4 outputs are supplied via the load supply.
The U
and U
voltages are galvanically isolated.
Q1
Q2
The connection cable for the output module load supply must
meet the following requirements:
W
Cable socket: M12x1, 4-pin, A-coded without center hole
(to ensure correct plug-in connection)
W
Cable cross-section: per wire > 0.5 mm
W
Length: Max. 20 m
1. Set up the correct pin assignment (see Table 15) on the plug
connections if you do not use pre-assembled cables.
2. Connect the load supply using the M12 plug.
Assignment
Not connected
Output signal
Reference potential
Output signal
Not connected
Connected to shield potential
NOTICE
2
85
Assembly