DRIVE CONFIGURATION

To adjust system settings, make sure power is off for five minutes, and remove the cover. Then, power
the drive to make menu and dip switch changes. When changes are complete, power off the drive before
replacing the cover.

DIP Switch Settings

DIP switch changes can be made with the drive powered on
and will take effect immediately.
Basic Setup (DIP SW1 — Position 1)
For basic set-up, DIP SW1 Position 1 (FE Connect - SubDrive Connect Plus mobile app switch) must be in
the O O F F F F (down) position for DIP switch settings to be recognized.
The mobile app can still have values to program the drive in the event the dip switch is turned ON.
However, while the DIP switch is OFF, the mobile app will never override the physical dip switch
values.
To program the drive electronically using the mobile app, DIP SW1 Position 1 must be in the O O N N (up)
position.
This setting disables DIP switch control and enables mobile app programming to override any man-
ual DIP switch settings.
Refer to
"FE Connect Mobile Application" on page 39
NOTE: The menu-based settings can be changed regardless of the position of this DIP switch.
Carrier Frequency Switch (DIP SW1 – Position 2)
In CEN applications where audible electrical noise can be heard from the motor, increasing the carrier
frequency (CF) can help reduce or eliminate electrical audible noise.
Carrier frequency setting is 2.5 kHz when the switch is in the O O F F F F (down) position.
Carrier frequency setting is 8 kHz when the switch is in the O O N N (up) position.
NOTE: SUB drive models (filtered drives) do not allow 8 kHz.
Pipe Fill Switch (DIP SW1 – Position 3)
When enabled, the Pipe Fill (PF) feature will run the motor at reduced speed while the pipes fill with
water. This can reduce water hammer in some systems, building up pressure in a controlled manner.
The Pipe Fill feature is disabled when the switch is in the O O F F F F (down) position.
The Pipe Fill feature is enabled when the switch is in the O O N N (up) position.
NOTE: Additional configuration of the Pipe Fill feature is available in the mobile app.
for more information.
DRIVE CONFIGURATION
DIP Switch Settings
27