Power Wiring Connections

WARNING
Contact with hazardous voltage could result in death or serious
injury.
Disconnect and lock out all power before installing or servicing equipment.
Make sure that all DC bus capacitor voltage has dissipated for several minutes after VFD
power is disconnected before working on wiring.
Connect the motor, the drive, metal plumbing, and all other metal near the motor or cable
to the power supply ground terminal using wire no smaller than motor cable wires.
Close any open conduit holes before finishing installation,
All wiring must comply with the National Electrical Code and local codes.
Incoming Power Supply
NOTICE
Risk of damage to VFD, or malfunction can occur.
Power source line to line, and line to ground voltages must be measured before connect-
ing the drive.
If a Corner-Grounded Delta power supply is used, all EMC jumpers at J10 and J11 must be
removed to prevent drive damage.
If an Open Delta Power Supply is used, the drive must be derated by 50% to prevent drive
damage and fault tripping.
Ensure that the system is properly grounded all the way to the service entrance panel, per
the NEC. Improper grounding may result in loss of voltage surge protection and interfer-
ence filtering.
Use only copper wiring rated for 600 V with 75 °C insulation.
Power Board EMC Jumper Locations:
1. J10 Jumper (two jumpers here)
2. J11 Jumper (two jumpers here)
Before connecting power to drive, test incoming supply voltages to meet nameplate ratings as follows:
Model
230 VAC
460 VAC
If any line to line voltage measures outside these ratings, do not use the drive on the incoming
power supply. Add a suitably-sized transformer to bring the voltages within these limits.
If line to line voltage is imbalanced, or line to ground voltage is low on one phase, this may be an
Open Delta Power Supply. This could cause I I n n p p u u t t P P h h a a s s e e L L o o s s s s ( ( F F 3 3 1 1 ) ) .
If one or more line to ground voltage measures 0 V or less than noted above, check system fuses. If
fuses are good, this may be a Corner-Grounded Delta Supply.
Line to Line VAC
190–253 (208–230 ±10%)
414-506 (460 ±10%)
ELECTRICAL INSTALLATION
Power Wiring Connections
Line to Ground VAC
Less than or equal to 253
Less than or equal to 506
23