MANUAL INSTALLATION AND OPERATION WFP-75 8411 ENGLISH
OF 40)
8.5
Facing
Non combustible finishing materials such as brick or ceramic can be glued to the facade of the
fireplace. Do not put a seal between the faceplate and the finishing material to facilitate removal
of the facaplate, if necessary.
R
8.6
Combustible Shelf Installation
A combustible shelf with a depth of 6" (152 mm)
(C) can be installed at least 58" (1,47 m) (B)
from the base of the fireplace.
Different shelf sizes are listed in the following
table.
Positioning and depth
B
58" (1,47 m)
60" (1,52 m)
62" (1,58 m)
64" (1,63 m)
No shelf may be installed lower than 58" (1.47 m)
from the base of the fireplace.
For a shelf dimension that does not appear in the
table, add 52" (1,32 m) to the depth of the shelf
to find the safe position of the shelf.
The height (A) should always be 80" (2.03 m)
from the base of the fireplace.
WFP-75 8411
Stove Builder International Inc. | 46345 | Rev: Apr 13 2020 12:33PM | Uncontrolled Copy
O
Q
P
of the the shelf
C
6" (152 mm)
8" (203 mm)
10" (254 mm)
12" (305 mm)
Combustibles materials
allowed in this zone
Non combustible material
only in this zone
O : 80" (2032 mm)
P : 36 ¾" (934 mm)
Q : 1 ¼" (32 mm)
R : 1 ¼" (32 mm)
45°
C
C
A
B
B
48"
1219mm
(25
A
Page 25