MANUAL INSTALLATION AND OPERATION WFP-75 8411 ENGLISH
OF 40)
9.3
Installation
The chimney manufacturer's installation manual takes precedence over the following installation
instructions. To ensure a safe installation, please refer to it. Some non-illustrated parts may be
required.
9.3.1
General Advices
• This wood burning fireplace has optimum performance and efficiency when connected to a
chimney with a 6" (150 mm) diameter flue, only the chimneys listed in the
• To insure a good draft, it is recommended to have a length of 18" (457 mm) from the top of
the unit to the first offset. However, starting using a 30° or 45° (Canada Only) elbow is also
approved.
• A CHIMNEY VENTING A FIREPLACE SHALL NOT VENT ANY OTHER APPLIANCE.
• The minimum height of the chimney system is 15 feet (4.6 m) from the base of the appliance to
the chimney cap. If only the minimum height of the chimney system is installed, the operating
conditions must be optimal (interior chimney, minimum height of 18" (457 mm) before any
deviation, etc.).
• The chimney must have at least one support. The maximum chimney length that should be
supported by the fireplace is 9 feet (2.75 m) for 2" Solid Pack chimney (5 cm) and 12 feet
(3.7 m) for 1" Solid Pack chimney.
• The chimney must extend at least 3 ft. (92 cm) above its point of contact with the roof and at
least 2 ft. (61 cm) higher than any wall, roof or building within 10 ft. (3.1 m) of it. .
MORE THAN 10' (3.1 M)
10' (3.1 M)
2' (0.61 M)
MINIMUM
CHIMNEY: 3' (0.92 M)
MINIMUM
CHIMNEY
• Avoid deviations as much as possible, especially the sharp ones. Each deviation adds
restriction to the system and can lead to draft problems.
• If the chimney extends higher than 5 ft. (1.5 m) above its point of contact with the roof, it must
be secured using a roof brace.
• A rain cap must be installed on top of the chimney
• For installations where more than one chimney is located in the same non-chase or within the
same area, their terminations must be separated by at least 16" (410 mm) horizontally, and
18" (460 mm) vertically. This separation is to prevent smoke migrating from one chimney to
another.
WFP-75 8411
Stove Builder International Inc. | 46345 | Rev: Apr 13 2020 12:33PM | Uncontrolled Copy
LESS THAN 10' (3.1 M)
2' (0.61 M)
MINIMUM
CHIMNEY: 3' (0.92 M)
MINIMUM
RIDGE
NOTE: HEIGHT ABOVE ANY
ROOF SURFACE WITHIN
10' (3.1 M) HORIZONTALLY
CHIMNEY
LESS THAN 10' (3.1 M)
CHIMNEY: 3' (0.92 M)
2' (0.61 M)
MNIMUM
2' (0.61 M)
MINIMUM
WALL OR
PARAPET
CHIMNEY: 3' (0.92 M)
CHIMNEY
CHIMNEY
table
can be used.
MORE THAN 10' (3.1 M)
NOTE: NO HEIGHT
ABOVE PARAPET
MINIMUM
SHALL BE REQUIRED
WHEN DISTANCE
FROM WALLS OR
PARAPET IS MORE
THAN 10' (3.1 M)
WALL OR
PARAPET
MINIMUM
CHIMNEY
Page 27
(27