OPERATION AND FUNCTION
Menu 4.00: Information (display of current settings and
switchgear data)
No.
Description
4.14
Running time pump 2
4.15
Running time pump 3
Switching cycles of the switch-
4.17
gear
4.18
Switching cycles of pump 1
4.19
Switching cycles of pump 2
4.20
Switching cycles of pump 3
Serial number of the switchgear
(display changes between the
4.22
fi rst and second 4 digits of the
serial number)
4.23
Switchgear type
4.24
Software version
4.25
Set rated current pump 1 [A]
4.26
Set rated current pump 2 [A]
4.27
Set rated current pump 3 [A]
Rated current pump 1 [A]; display
4.29
changes between L1, L2 and L3
Rated current pump 2 [A]; display
4.30
changes between L1, L2 and L3
Rated current pump 3 [A]; display
4.31
changes between L1, L2 and L3
Menu 5.00: Installation (basic settings of the switchgear)
No.
Description
Operating mode
5.01
Values: fi ll, drain
Factory setting: drain
Number of pumps
5.02
Value range: 1...3
Factory setting: 2
Installation and operating instructions Salmson-Control EC-L
Menu 5.00: Installation (basic settings of the switchgear)
No.
Display
Standby pump **
5.03
Values: off, on
Factory setting: off
Sensor type for level
measurement **
5.07
Values: Float, Level, Bell, Opt01
Factory setting: Level
Sensor measuring range
5.09
Value range: 0.25...12.50 m
Factory setting: 2.50 m
Alarm for deactivating the device
via "External Off" On/Off **
5.39
Values: off, on
Factory setting: off
Pump kick On/Off **
5.40
Values: off, on
Factory setting: off
Pump kick for "External Off"
allowed **
5.41
Values: off, on
Factory setting: on
Interval between
pump kicks **
5.42
Value range: 0...336 h
Factory setting: 24 h
Running time of pump on pump
kick **
5.43
Value range: 0...60 s
Factory setting: 5 s
Activation delay after power
failure of the switchgear **
5.44
Value range: 0...180 s
Factory setting: 3 s
Dry-running level (Drain) or min.
water level (fi ll)
5.50
Value range: 0...12.50 m
Factory setting: 0.12 m
High water level
5.51
Value range: 0...12.50 m
Factory setting: 1.25 m
Maximum running time of an
individual pump
5.57
Value range: 0...60 min
Factory setting: 10 min
Collective run signal function
(SBM) **
5.58
Values: on, run
Factory setting: run
Collective fault signal function
(SSM) **
5.59
Values: fall, raise
Factory setting: raise
Display
Delay dry-running protection
5.62
Value range: 0...180 s
Factory setting: 60 s
Ex-mode operation On/Off **
5.64
Values: off, on
Factory setting: on
Description
Display
English