WATER SUPPLY AND DRAIN LINE SIZING/CONNECTIONS

! Caution
Plumbing must conform to state and local codes.
Location
Water Temperature
35°F (2°C) Min.
Ice Making
Water Inlet
90°F (32°C) Max.
35°F (2°C) Min.
90°F (32°C) Max.
Water Cooled
Condenser
Ice Making
Water Drain
Base Drain
Bin Drain
Large Capacity
Bin Drain
FPT = Female Pipe thread

COOLING TOWER APPLICATIONS

(Water-Cooled Models Only)
A water cooling tower installation does not require
modification of the ice machine. The water regulator
valve for the condenser continues to control the
refrigeration discharge pressure.
It is necessary to know the amount of heat rejection, and
the pressure drop through the condenser and water
valves (inlet and outlet) when using a cooling tower on
an ice machine.
Water entering the condenser must not exceed 90°F
(32°C).
Water flow through the condenser must not exceed
5 gallons (19 liters) per minute.
Part Number 000006505 12/10
Water Pressure
Min/Max
20 / 80 psi
140 / 550 kPa
Standard
20 / 150 psi
140 / 1030 kPa
High Pressure Option
20 / 350 psi
140 / 2410 kPa
----
----
----
----
----
----
----
----
ID = Inside Diameter
Ice Machine Fitting
3/8" FPT
S3000C 1/2" FPT
1/2" FPT
1/2" FPT
S3000C 1" FPT
S3000C 1" FPT
3/4" FPT
1" FPT
Min = Minimum
Allow for a pressure drop of 8 psi (1030 kPa)
between the condenser water inlet and the outlet of
the ice machine.
Water exiting the condenser must not exceed 110°F
(43°C).
Do not connect to the potable water filter system.
Contact your distributor if your water pressure is
greater than 150 psig (1030 kPa). A special order
condensing unit is available that allows water
pressure up to 350 psig (2410 kPa).

Important

The Commonwealth of Massachusetts requires that
all water-cooled models must be connected only to a
closed loop, cooling tower system.
Installation
Minimum Tubing Size Up to
Ice Machine Fitting
3/8" (10 mm) ID
S3000C 1/2" (13 mm) ID
1/2" (13 mm) ID
1/2" (13 mm) ID
S3000C 1" (25 mm) ID
S3000C 1" (25 mm) ID
3/4" (19 mm) ID
1" (25 mm) ID
Max= Maximum