Installation
Step 6 Open Lineset and Receiver Valves
You will not hear refrigerant flow when the valves are
opened. Refrigerant will not flow until the toggle switch is
placed in the ice position and the solenoid valve opens.
All valve caps must be reinstalled, tightened and leak
checked to assure no refrigerant leakage exists.
Counterclockwise opens all valves:
A. Refer to chart and open the suction and liquid
line shut off valves the correct number of 360
turns.
Valve Tubing Size
3/8"
1/2" 5/8" 3/4"
7/8"
B. Open the receiver service valve until
backseated (two valves on the S3000C).
USE ALLEN WRENCH TO OPEN
(TURN COUNTERCLOCKWISE)
LIQUID AND SUCTION LINE
SHUT OFF VALVES
S0600C/S0800C/S1000C/S1200C
USE ALLEN WRENCH
TO OPEN (TURN
COUNTERCLOCKWISE)
LIQUID AND SUCTION
LINE SHUT OFF
VALVES
IB0600C/IB0800C/IB1000C
14
Number of Turns To Open
6
10
14
.
.
USE ALLEN WRENCH
TO OPEN (TURN
COUNTERCLOCKWISE)
LIQUID AND SUCTION
LINE SHUT OFF
VALVES
°
USE ALLEN WRENCH
TO OPEN (TURN
COUNTERCLOCKWISE)
LIQUID AND SUCTION
LINE SHUT OFF
VALVES
After opening suction, discharge and receiver
service valves, refrigerant pressure will not be
detected until the toggle switch is placed in the ice
position and the solenoid valves energize.
S1470C/S1870C/S2170C
S3000C
! Caution
Part Number 000006505 12/10