Normal Operation - Burkert 3003 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

learning mode
specify end positions
Press <OPEN> and <CLOSE>
pushbutton and switch on the card
(hold down pushbutton). The RED
and the GREEN LEDs light up.
G
R
Release <OPEN> and <CLOSE>
pushbutton.
Both LEDs go out.
Learning mode is selected.
Press <CLOSE> pushbutton to move
the shut-off valve into the closed
R
position.
The RED LED lights up.
Press <MEM> and <CLOSE> push-
button to save the closed position.
R
The RED LED lights up 2x.
Press <OPEN> pushbutton to move
the shut-off valve into the open
G
position.
The GREEN LED lights up.
Press <MEM> and <OPEN> push-
button to save the open position.
G
The GREEN LED lights up 2x.
16
english
Type 3003
Installation
specify end positions
All positions are now saved.
Disconnect the card from the power
supply.
8.8. normal operation
display normal operation
Switch on card.
The GREEN LED lights up 3x to indicate that the
G
start process has been implemented correctly.
In normal operation the GREEN LED lights up
G
when the rotary actuator opens the shut-off valve.
The RED LED lights up when the rotary actuator
R
closes the shut-off valve.
If neither of the LEDs is lit, the actuator is not
G
R
actuated.
The RED and the GREEN LEDs light up if the
torque is too high and the rotary actuator stops.
G
R
Change direction of rotation of the rotary
actuator or switch over the voltage OPEN/
CLOSED to restart the rotary actuator!

Publicité

Table des Matières
loading

Table des Matières