Rotary Actuators With Integrated Emergency; Technical Data; Electric Wiring; Circuit Board - Burkert 3003 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Rotary actuators with integrated emergency reset
9.
roTary acTuaTors WiTh
inTeGraTed emerGency reseT
9.1. Technical data
Voltage
18 V DC
Currant nominal 0.8 A
Max. Current
2.4 A
Charging time
max. 14 h
Feedback relay for charge state
Permitted ambient temperature
9.2. electric wiring
18 V DC Battery Block
E -
black wire
F +
F +
Safety block
red wire
E -
Load state
feedback
65
66
Loaded battery: closed contact.
A
Configuration
OR
Fig. 10: Electric wiring
Type 3003
24 V DC - 1 A max
-10 °C - +40 °C
Pilot and power supply
card
17
17
18
18
1
2
3
B
A
On-Off- Mode
On
B
N
Ph
-
+
configuration a or b
A-standard mode: If the actuator is controlled with a programmable
controller, the feedback of the charge state can be connected to it.
B-mode - increased safety (if the feedback relay is used, terminals
65 and 66): The actuator does not actuate the valve unless the safety
block is loaded.
9.3. circuit board
D
E
B
C
Fig. 11: Diagram: Circuit board
english
A
17

Publicité

Table des Matières
loading

Table des Matières