8.7. parameterization steps
specify direction of rotation of the shut-off valve
normal direction of rotation (preset)
Press <OPEN> pushbutton and switch on
the card (hold down pushbutton).
The GREEN LED lights up.
G
Release <OPEN> pushbutton and disconnect
the card from the power supply.
reverse direction of rotation
Press <CLOSE> pushbutton and switch on
the card (hold down pushbutton).
The RED LED lights up.
R
Release <CLOSE> pushbutton and disconnect
the card from the power supply.
specify control signal type
control signal when voltage 0 – 10 V
Press <MEM> pushbutton and switch on the
card (hold down pushbutton).
The RED LED lights up 3x.
R
Release <MEM> pushbutton and disconnect
the card from the power supply.
Type 3003
Installation
control signal when current 0 – 20 ma
Press <MEM> and <OPEN> push-
button and switch on the card (hold
down pushbutton).
The RED LED lights up 3x.
R
Release <MEM> and <OPEN> push-
button and disconnect the card from
the power supply.
control signal when current 4 – 20 ma (preset)
Press <MEM> and <CLOSE> push-
button and switch on the card (hold
down pushbutton).
The RED LED lights up 3x.
R
Release <MEM> and <CLOSE>
pushbutton and disconnect the card
from the power supply.
english
15