8.3

Wiring the device

danger
risk of injury due to electrical voltage.
▶ Shut down the electrical power source of all the conductors and
isolate it before carrying out work on the system.
▶ All equipment connected to the 8619 shall be double insula-
ted with respect to the mains according to the standard IEC
61010-1:2010.
▶ Observe all applicable accident protection and safety regula-
tions for electrical equipment.
• Use a filtered and regulated 12-36 V DC power supply.
• Make sure the installation is equipotential. See chap.
8.3.2.
• Use shielded cables with a temperature limit of 80 °C
minimum.
• Do not install theconnection cables near high voltage or
high frequency cables; If this cannot be avoided, observe
a min. distance of 30 cm.
• Protect the power supply of the device with a 100 mA
time-delay fuse and a switch.
• Protect the power supply of each transistor output with a
750 mA fuse.
16
English
Type 8228
Installationandwiring
8.3.1
Assembling the male or female fixed
connector (available as an accessory)
4
3
2
1
5
Fig. 9:
Assembling the M12 multi-pin connector (not provided)
Unscrew the nut [1] on the
body [4].
Insert the cable into the nut
[1], the cable clamp [2] and
the seal [3], and then into
the body [4].
Strip 20 mm of the cable.
Cut the central wire (earth)
so that its length is equal to
11.5 mm.
Expose 5.5 mm of the wires
on the stripped cable.
Put each wire into the
appropriate terminal of
the terminal block [5] (see
chap. 8.3.3 or 8.3.4).
Tighten the terminal block
[5] wired to the body [4].
Tighten the connector nut
[1].

Publicité

Table des Matières
loading