8.3
Wiring the device
danger
risk of injury due to electrical voltage.
▶ Shut down the electrical power source of all the conductors and
isolate it before carrying out work on the system.
▶ All equipment connected to the 8619 shall be double insula-
ted with respect to the mains according to the standard IEC
61010-1:2010.
▶ Observe all applicable accident protection and safety regula-
tions for electrical equipment.
• Use a filtered and regulated 12-36 V DC power supply.
• Make sure the installation is equipotential. See chap.
8.3.2.
• Use shielded cables with a temperature limit of 80 °C
minimum.
• Do not install theconnection cables near high voltage or
high frequency cables; If this cannot be avoided, observe
a min. distance of 30 cm.
• Protect the power supply of the device with a 100 mA
time-delay fuse and a switch.
• Protect the power supply of each transistor output with a
750 mA fuse.
16
English
Type 8228
Installationandwiring
8.3.1
Assembling the male or female fixed
connector (available as an accessory)
4
3
2
1
5
Fig. 9:
Assembling the M12 multi-pin connector (not provided)
→
Unscrew the nut [1] on the
body [4].
→
Insert the cable into the nut
[1], the cable clamp [2] and
the seal [3], and then into
the body [4].
→
Strip 20 mm of the cable.
→
Cut the central wire (earth)
so that its length is equal to
11.5 mm.
→
Expose 5.5 mm of the wires
on the stripped cable.
→
Put each wire into the
appropriate terminal of
the terminal block [5] (see
chap. 8.3.3 or 8.3.4).
→
Tighten the terminal block
[5] wired to the body [4].
→
Tighten the connector nut
[1].