4.4.6.2
Teach-In for volume
This function allows the relationship between the transmitter display and real measurement
to be defined by volume. This can be completed by entering:
The dimensions of the tank or vessel (for regular shaped tanks and vessels only) - (C)
-
or
The input of up to 12 distances and associated volumes (for irregular tanks or vessels)
-
- (D) or
The input of up to 12 known volumes with distance measurement by the transmitter - (E)
-
Please pay attention to the units selected and the measured values entered within this opti-
on as the transmitter only uses meters and feet to calculate the volume.
TEACH-IN
TEACH N
0......9
TEACH Y
C
- INPUT OF TANK DIMENSIONS
This function identifies the relationship by entering the dimensions of the tank/vessel and
the present volume.
Within this function it is possible to select 1 of 5 options depending on the application
-
and shape of the tank/vessel.
Select one of the pre-determined shapes - 'VER CYL', 'CUBE' or 'SPHERE' and enter the
-
dimensions required.
If ' MANUAL' is selected the transmitter automatically advances to the next option D to
-
allow the user to manually input the distance measurements with associated volumes.
The option 'SPECIAL' allows the user to select the last type E volume Teach-In procedure
-
completed.
This procedure allows the transmitter to compute the volume of the liquid contained in the
tank/vessel according to the measured level of the fluid.
CALIBRATION MENU
VER.CYL
ENTER
CUBE
0......9
SPHERE
MANUAL
SPECIAL
Volume Teach-In
E
ENTER
procedure
40
Input of tank dimen-
C
sions
Manual input of
D
distances and asso-
ciated volumes