6.2 HORIZONTAL CYLINDRICAL TANK VALUE CONVERSIONS

For the calculation and input of the measured values for a horizontal cylindrical tank, both
the level % and Volume % relationships have to be calculated and then entered within the
manual input of distances and associated volumes procedure.
To calculate the values a table below has been provided to assist with the calculations.
Level in %
0
10
20
30
40
50
60
70
80
90
100
Steps for value calculation
Identify the maximum and minimum level and volume for the application.
-
Enter the maximum (100%) and minimum (0%) volume and level within the table.
-
Calculate the level values at the respective level percentages for the application
-
(90% - 0%).
Calculate the volume values for the respective volume percentages by multiplying
-
the maximum volume of the application by the volume % within the table and
dividing by 100.
After calculating the values perform a volume Teach-In - D.
INFORMATION
Level (chosen unit)
60
Volume in %
Volume (chosen
0,00
5,20
14,24
25,23
37,35
50,00
61,64
74,77
85,76
94,79
100,00
unit)