10.10 Communication interfaces

®
64
TAPCON
230
Description
Interfaces
COM X1
Only available for the
TAPCON® 230 Pro, Expert and
AVT variants.
COM X2
COM X3
Only available for the
TAPCON® 230 Expert and AVT
variants.
COM X4
Only available for the
TAPCON® 230 Expert and AVT
variants.
COM X5
Only available for the
TAPCON® 230 Expert and AVT
variants.
COM-X6
Only available for the
TAPCON® 230 Pro, Expert and
AVT variants.
7820658/02 EN
Assembly for converting interfaces and media
1x RS232/RS485 (RJ45): COM X1
2x Ethernet (RJ45): COM X2, COM X5
1x RS232 (D-SUB): COM X3
1x duplex LC (SFP): COM X4
1x plug terminal 10-pin: COM X6
Internal system interface for connecting the
COM X6 interface to the central processing
unit (CPU)
Internal system interface for connection the
front interface to the central processing unit
(CPU)
Serial SCADA interface RS232
▪ 9-pin D-SUB connector
SFP module for converting Ethernet (RJ45) to
fiber-optic cable for SCADA
▪ Max. 2000 m
▪ 100 Mbps
▪ Light-emitting diode: class 1
▪ Wave length: 1310 nm
▪ Max. optical output power: <1 mW (in accor-
dance with IEC 60825-1:2014)
Ethernet connection for SCADA
10-pin plug terminal
▪ Tap position capture via resistor contact se-
ries
▪ CAN bus
▪ Serial SCADA interface RS485
▪ Electrically isolated