Description Des Interfaces Se Référant À Cei 61850; Aperçu Des Composants; Eléments De Données Spécifiques Au Tapcon® 260 - MR TAPCON 260-RTE Instructions De Service

Table des Matières

Publicité

7
Description des interfaces se référant à CEI 61850
7
Description des interfaces se référant à CEI 61850
7.1
Aperçu des composants
• TAPCON® 260
• Carte SID
• Câble réseau avec fiche RJ45
36
Declaration
Mod
Mode
Beh
Behaviour
Health
health
NamPlt
name plate
PhyNam
name plate
PhyHealth
health
Proxy
Indicates proxy
Mod
Mode
Beh
Behaviour
Health
Health
NamPlt
Name plate
Loc
Local operation
TapChg
Change Tap Position
ParOp
Parallel/Independend
LTCBlk
Block Automatic Control
Auto
Automatic/Manual operation
HiTapPos
High tap position
LoTapPos
Low tap position
CtlV
Control Voltage
LodA
Load Current (percentage of nominal load current)
BndCtr
Band center voltage
BndWid
Band width voltage (as percent of nominal voltage, FPF presumed)
CtlDlTmms Control intentional time delay (FPF presumed, in seconds)
LDCR
Line drop voltage due to line resistance component (voltage)
LDCX
Line drop voltage due to line reactance component (voltage)
BlkLV
Control voltage below which auto Lower commands blocked (voltage)
LimLodA
Limit Load Current (LTC Block Load Current, percentage)
Line Drop Compensation is R and X or Z model (0=R and X, 1=Z
LDC
compensation)
TmDlChr
Time delay linear or inverse characteristic (0=lin., 1=inv.)
Line drop voltage due to line total impedance (percentage of nominal
LDCZ
voltage)
RegAuto
REG.AUTO (Regulation AUTO)
K2Adj
VC+DVC2 (Coefficient for adjustment of desired voltage Uref2)
K3Adj
VC+DVC3 (Coefficient for adjustment of desired voltage Uref3)
K4Adj
VC+DVC4 (Coefficient for adjustment of desired voltage Uref4)
BndCtrSel1 VC+DVC1 (Band center selection)
BndCtrSel2 VC+DVC2 (Band center selection)
BndCtrSel3 VC+DVC3 (Band center selection)
BndCtrSel4 VC+DVC4 (Band center selection)
MotDrv
Motor drive active
VoltViol
U.ANORMA (group signal lower U, U higher)
INRegul
IN.REGUL (AVR Blocking - Overload)
StepErr
NON.BLOC (tap position refereeing w.o success)
ParErr
défaut configuration (Configuration error)
UnderV
undervoltage
OverV
overvoltage
UnderVReg tension basse (lower U)
OverVReg
tension haute (U higher)
RegBloc
blocage régleur réussi (AVR Blocking - Successful)
CBOpen
régulation HS-DJ THT ouvert (Automatic OFF - CB HV open)
TTErr
Fusion fusible (Automatic OFF - Blown Fuse)
InvalV
absence tension (Automatic OFF - Absence of voltage)
StepUpper
régleur en position haute (OLTC - Upper end position)
StepLower
régleur en position basse (OLTC - Lower end position)
DFReg
DF.REGUL (Anomaly OLTC)
7.2
Eléments de données spécifiques au
TAPCON® 260
Description
TAPCON® 260 RTE
readable/
writeable
R
R
R
R
R
R
R
R
R
R
R
R
R&W
R&W
R&W
R
R
R
R
R
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R&W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1801010/02 FR

Publicité

Table des Matières
loading

Table des Matières