6 Mounting
6.4.5.4 Ethernet interface
Maschinenfabrik Reinhausen GmbH 2021
4. Connect the COM-X5 to the CPU-X2 using the supplied patch cable.
Figure 30: Connecting CPU-X5 and COM-X2
Serial fiber-optic cable
You will need the CM-0847 FO converter if you want to connect your control
system via the serial fiber-optic cable.
► Connect the serial fiber-optic cable and the converter to the CPU-X5 inter-
face.
► Connect the Ethernet cable (RJ45 connector) to the COM-X3 interface.
6.4.6 Wiring voltage measurement/current measurement UI
You must fuse the voltage measurement circuit in accordance with the con-
ductor cross section used. You can use the following fuse types:
Standard
Rated voltage
Rated current
7820658/02 EN
Miniature circuit breaker
IEC 60947-2
400 V (L-L) or 230 V (L-N)
30 mA...16 A
Safety fuse
IEC 60269
®
TAPCON
230
43