Auxiliary power supply AUX DC DI 110 V DC for digital inputs
The auxiliary power supply is used exclusively for the acquisition of up to 16
floating contacts.
Output voltage
Max. output power
Overvoltage category
Surge test voltage
Fuse
Table 11: Auxiliary power supply
Interface
Table 12: Connection X8

10.5 Voltage measurement and current measurement

Voltage measurement TAPCON® 230 basic/pro/expert
Measuring range
Nominal voltage U
Accuracy
Measurement category
(IEC 61010-2-30)
Continuous overvoltage
Surge test voltage
Voltage measurement TAPCON® 230 AVT
Measuring range (switchable) 132...280 V AC
Nominal voltage U
Accuracy
Measurement category
(IEC 61010-2-30)
U
N
5 W
OC III
5 kV, 1.2 µs/50 µs (IEC 60255-27)
250 V AC, 0.08 A, 5 x 20 mm, TT char-
acteristic (very slow acting), breaking ca-
pacity L (min. 35 A), operating tempera-
ture -30°C...+85°C)
Pin
Description
2
L
1
N
20...197 V AC
100 V AC
N
< ±0.3% x U
N
CAT III at an altitude of 3,000 m
550 V AC
5 kV, 1.2 µs / 50 µs (IEC 60255-27)
230 V AC
N
< ±0.3% x U
N
CAT III at an altitude of 2,000 m
CAT II at an altitude of 3,000 m
7820658/02 EN
10 Technical data
: 110 V DC ± 2% (short-circuit proof)
in the operating temperature range
228...510 V AC
400 V AC
in the operating temperature range
Maschinenfabrik Reinhausen GmbH 2021