6 Mounting
6.4.2.3 Wiring requirement in control cabinet
Maschinenfabrik Reinhausen GmbH 2021
Figure 19: Recommended connection of the shielding
1 Connection of the shielding via a
single conductor
Note the following when wiring in the control cabinet:
▪ The control cabinet where the device will be installed must be prepared in
accordance with EMC requirements:
– Functional division of the control cabinet (physical separation)
– Constant potential equalization (all metal parts are joined)
– Line routing in accordance with EMC requirements (separation of lines
which cause interference and those susceptible to interference)
– Optimum shielding (metal housing)
– Overvoltage protection (lightning protection)
– Collective grounding (main grounding rail)
– Cable bushings in accordance with EMC requirements
– Any contactor coils present must be interconnected
▪ The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground connec-
tion.
▪ Signal lines and power lines/switching lines must be laid in separate cable
ducts.
▪ The device must be grounded on the provided screw, the protective
ground connection, with a ground strap (cross-section of min. 8 mm²
2
(0.32 in
).
7820658/02 EN
2 Full-surface connection of the
shielding
®
TAPCON
230
35