NOTICE
Destruction of the product
An incorrect connection of the input or output channels can lead to destruction of the product or connected components.
Repeated and strong overloading of the channels can destroy the product.
Ensure that the design values are adhered to.
3.11
Communication
Information on the physical properties of the communication interfaces can be found in the technical specifications of the
respective products.
3.12
Cables and shielding
The suitable cable types, cable lengths and cross-sections can be found in the technical specifications of the product.
To meet the requirements in the power plant sector (damped oscillatory wave, asymmetrical conducted disturbance
variables), the field wiring for the I/O modules must be executed as indicated in the table below:
Table 3-1
Field wiring for I/O modules according to IEC 61000-4-16 and IEC 61000-4-18
I/O module
DI 16x24VDC HA
DI 16x24VDC NPN
DI 32x24VDC HA
DI 16xNAMUR HA
F-DI 16x24VDC HA
F-DI16xNAMUR
DI 8x24..125VDC HA
DI 8x230VAC HA
DQ 8x 24V...230VAC/2A
DQ 16x24VDC/0.5A HA
DQ 32x24VDC/0.5A HA
F-DQ 10x24VDC/2A PP HA
RQ 4x120VDC-230VAC/5A CO HA
AI-DI16/DQ16x24VDC HART HA
AI 4xI HART ISOL HA
AI 16xI 2-wire HART HA
AI 16xTC/8xRTD 2-/3-/4-wire HA
AQ 4xI HART ISOL HA
AQ 8xI HART HA
F-AI 8xI 2-/4-wire HART HA
AI 8xU/I/TC/4xRTD 2-/3-/4-wire HA
AI 16xl 2-wire HA
To meet the requirements of NE21, execution with or without shielding is possible.
The signal cable for the D-SUB terminal block must satisfy the following conditions:
The D-SUB cable must be shielded.
The cross-section of the cores must be at least 0.25 mm² (at least 0.5 mm² when using the I/O module F-DQ 10x24
VDC/2 A).
Only operate the cable and the D-SUB plug-in connector under the conditions, especially the thermal conditions,
approved for the products.
If you are operating fail-safe I/O modules, measures for short-circuit fault exclusion in accordance with ISO 13849-2 must
be taken into account.
Cables emerging from the enclosure/control cabinet require strain relief.
ET 200SP HA Distributed I/O System
A5E52222765-AB, 11/2024
Article number
6DL1131-6BH00-0PH1
6DL1131-6BH60-0PH1
6DL1131-6BL00-0PH1
6DL1131-6TH00-0PH1
6DL1136-6BA00-0PH1
6DL1136-6TH00-0PH1
6DL1131-6DF00-0PK0
6DL1131-6GF00-0PK0
6DL1132-6FF00-0PK0
6DL1132-6BH00-0PH1
6DL1132-6BL00-0PH1
6DL1136-6DA00-0PH1
6DL1132-6HD50-0PK0
6DL1133-6EW00-0PH1
6DL1134-6UD00-0PK0
6DL1134-6TH00-0PH1
6DL1134-6JH00-0PH1
6DL1135-6UD00-0PK0
6DL1135-6TF00-0PH1
6DL1136-6AA00-0PH1
6DL1134-6AF00-0PH1
6DL1134-6GH00-0PH1
Execution of the field wiring
Unshielded / shielded
Unshielded / shielded
Unshielded / shielded
Shielded
Unshielded / shielded
Shielded
Unshielded / shielded
Unshielded / shielded
Unshielded / shielded
Unshielded / shielded
Unshielded / shielded
Unshielded / shielded
Unshielded / shielded
Shielded
Shielded
Shielded
Shielded
Shielded
Shielded
Shielded
Shielded
Shielded
45