6.
TEchnical daTa
6.1.
Operating conditions
Warning!
danger of explosion!
The controller Type 1094 EV has a protection class of IP00 and is
not designed for use in the explosion-protected area. If it is used
in the area of tank installations, a short-circuit in the controller
could cause an explosion.
•
If it used in the area of a tank installation, the controller Type
1094 EV must be installed in a control cabinet with an appropri-
ate protection class.
Permitted ambient temperature: -25 – +55 °C
Permitted air humidity:
noTE!
damage to device caused by icy or wet conditions!
Icy and wet conditions may damage the device and cause
malfunctions.
•
Protect device from icy and wet conditions caused by dew, etc.
12
(icing over not permitted)
5 – 85 %
(condensation not permitted)
English
Type 1094 EV
Technical Data
Protection class:
IP00, the electronics are designed for oper-
ation in the control cabinet only.
6.2.
conformity with the following
standards
CE mark compliant with
EMC generic emission standard
IEC-61000-6-1
IEC-61000-6-2
IEC-61000-6-3
IEC-61000-6-4
BImSchV
Bundes-Immissionsschutz-Verordnung
(Federal Emission Protection Ordinance)
21. BImSchV; Ordinance on the Restriction of
Hydrocarbon Emissions during the Refueling of
Vehicles
6.3.
general Technical data
Housing:
Open housing for installation on mounting rail in
accordance with DIN EN 50022 / DIN EN 50035 /
DIN EN 50045
Dimensions:
68 x 76 x 35 mm
Order number:
208373