Kessel EasyClean free NS15 Instructions De Pose Et D'utilisation page 56

Publicité

4
Installation
4.1
Transport information
Dismantle the pump and the pipes for easier installation. A leak test must be performed after reattachment of the pump
and the pipes.
The tank may only be transported on site using a forklift truck (lashed onto the transport pallet) or using a crane (illus-
trated lifting eyebolts).
When lifting, use the two transport eyebolts near the inlet and outlet. The tank may only be lifted when empty and with a
round sling.
Wire ropes or chains are not permitted.
CAUTION
Observe the weight of the grease separator ( see "Dimensions and weights", page 51).
4.2
Choose suitable installation location
Pre-requisites for the operation of separator systems:
Ensure aeration and/or ventilation of the room.
Set-up area level and capable of bearing sufficient load (see "Technical data", page 51 ).
Room temperature at least 15 °C.
Sealed floor covering with integrated drain.
Hot and cold water connections available.
Room height at least 60 cm higher than the grease separator, so that the inspection openings can be opened for cleaning
work.
At least 1 m free working space in front of the grease separator.
Inlet with calming section of at least 1 m (gradient 1: 50). Transition of on-site downpipe to calming section equipped with
2 x 45° bends.
If the inlet pipe is longer than 10 m horizontally, it must be vented separately.
4.3
Installing the pipes
Attachment of the refill inlet
Push the end of the refill inlet pipe up to the union nut.
If necessary, remove the clip from the mounting clamp for the refill inlet pipe.
Tighten the union nut on the refill inlet pipe by hand.
Check that the refill inlet pipe is correctly attached to the mounting clamp with the clip.
The refill inlet is ready for operation.
56 / 132
Installation and operating instructions
016-673