12 Troubleshooting
12.1 Procedure
Step 1: Check the system
In case of malfunctions, first check the system or the system part where the
u
product is installed. Check the following items:
• All connections. See g 9. Service.
• Settings. See
g 14. Technical
Step 2: Check the product
1. Make sure the system or system part is not under pressure or voltage.
2. Check the product based on the fault patterns described below.
3. Perform troubleshooting using the information under "Remedy".
If the malfunction cannot be eliminated as described under "Remedy": Disas-
semble the product and return it. See
4. After the malfunction has been eliminated; Put the system or product back
into operation.
12.2 Malfunction types
Error
Possible cause
No output pressure at the
No power supply connected
valves
to the product. See LED dis-
play.
No supply pressure available. Connect supply pressure.
Output pressure too low
Supply pressure too low.
Power supply for the product
not sufficient.
Air is audibly escaping
Leakage between product
and supply.
Pneumatics incorrectly con-
nected.
No addressing possible via
A save operation was trig-
the programming software
gered before the address was
set
LED UL/UA flashes green
The supply voltage is less
than the lower tolerance limit
(18 V DC) and more than
10 V DC
LED UL/UA illuminates red
The valve supply voltage is
less than 21.6 V DC
LED UL/UA is off
The supply voltage is less
than 10 V DC.
LED UL/UA flashes red
The supply voltage is greater
than 26.4 V DC.
LED DIAG flashes red
No module connected to the
product
Diagnostic message for open
load/short circuit at valve
available.
LED DIAG illuminates red
Diagnostic message available. Check the modules.
Internal connection error or
hardware error.
Product is not detected.
RUN LED flashes green
The product is in PRE-OPERA-
TIONAL state.
RUN LED flashes green (brief
Error in the PLC configuration. Check PLC configuration.
flashing)
LED RUN is off
The product is in INIT state.
LED RUN illuminates red
Product damaged.
LED ERR flashes red
No connection to network
participant. No communica-
tion via EtherCAT possible.
Error in the PLC configuration. Check PLC configuration.
AVENTICS™ EtherCAT | 570089-BAL-AA | English
data.
g 4.3 Returning the
product.
Remedy
Apply power supply on plug
connector X1S.
Check power supply polarity.
Switch on system compo-
nent.
Increase supply pressure.
Check LED on the product.
Apply sufficient power sup-
ply.
Check the supply connection.
Check the pneumatic connec-
tion.
1. Separate the power sup-
ply.
2. Establish the power sup-
ply.
Check power supply on plug
connector X1S.
Connect the module.
Check the connection of the
valves.
Contact manufacturer
Set the product to OPERA-
TIONAL state.
Set the product to OPERA-
TIONAL state.
Set the product to OPERA-
TIONAL state.
Replace product.
Check the connection.
Error
Possible cause
Synchronization error, prod-
uct automatically switches to
SAFE-OPERATIONAL state.
LED L/A IN or LED L/A OUT is
No data exchange possible.
off
Product has not been config-
ured in the control.
No connection to network
participant.
Connecting cable damaged.
Network participant dam-
aged.
Product damaged.
13 Disposal
Improper disposal will lead to pollution of the environment. Furthermore, the
materials can no longer be recycled.
Dispose of the product, the packaging and any escaping operating materials
u
in accordance with the applicable national regulations.
14 Technical data
This section contains an excerpt of the most important technical data. Further
technical data can be found on the product page in the Emerson store.
General
Dimensions
Weight
Material
Degree of contamination
Relative humidity
Ambient temperature for storage
min. ... max.
Ambient temperature during operation
min. ... max.
Max. number of valves
Max. height above sea level
Vibration resistance for EN 60068-2-6
wall mounting
Shock resistance for EN 60068-2-27 wall
mounting
Electrics
Degree of protection according to
EN 60529 / IEC 60529
Supply voltage
Valve supply voltage
Nominal current
Power supply connection type
Current consumption of the electron-
ics
Permissible ripple
Standards and directives complied with
Standard / directive Description
EMC directive
Electromagnetic compatibility of electric products and electronic
2014/30/EU
products
EN 60204-1
Safety of machinery – Electrical equipment of machines, Part 1: Gen-
eral requirements
EN 61000-6-2
Electromagnetic compatibility (EMC); part 6-2: Generic standards –
interference immunity for industrial environments
EN 61000-6-3
Electromagnetic compatibility (EMC); part 6-3: Generic standards –
Emission standard for equipment in residential environments
Remedy
Set the product to OPERA-
TIONAL state.
Connect network with the
control.
Configure the product in the
control.
Connect fieldbus connection
X7E1 or X7E2 to network par-
ticipant.
Replace connecting cable.
Replace network participant.
Replace product.
Specifications
45 mm x 97.2 mm x 27.25 mm
0.089 kg
Fiberglass reinforced polyamide
2
95 %, non-condensing
-25 ... 80 °C
-10 ... 50 °C
24 (48 coils)
2000 m
±0.35 mm displacement at 10 Hz ... 60 Hz,
5 g acceleration at 60 Hz ... 50 Hz
30 g with 18 ms duration,
3 shocks each direction
Specifications
IP65 when assembled
24 V DC ±25 %
24 V DC ±10 %
3 A
M12 A-coded, 4 pin or 5 pin
0.2 A
5 %
22