4 CONFIGURATION
BATCH CONTROLLER 8025
4.4.2 Unit
ENTER
ENTER
ENTER
m L .LITER
UNIT
BATCH
LIT/SEC
LITER
LIT/MIN
M3
LIT/H
0......9
US GAL
M3/MIN
IMP GAL
M3/H
UGAL/SEC
UGAL/MIN
UGAL/H
IGAL/SEC
IGAL/MIN
IGAL/H
ENTER
TOTAL
ENTER
LITER
M3
US GAL
IMP GAL
ENTER
K-FACTOR
Note: Return to the main menu is only available from the « TOTAL » Sub-Menu.
4.4.3 K-factor
The K-factor of the fitting is entered in this menu (see Instruction manual fitting type S020/
/S0301500/1501 if a Burkert sensor is used, else, refer to the specific instruction manual
of the sensor). The "Teach in" function allows to practically detemine the application
specific K-factor. The user only needs to run a known quantity through his system.
Example: In order to determine a quantity the most accurately possible, the user shall fill
a tank of 100 liters. When the message "TEACH YES" appears, he presses the Enter key to
start the measuring procedure. The message "FILL END" (end of filling) will appear. He then
switches on a pump or opens a valve. As soon as his tank is full, he switches off the pump
or closes the valve. Pressing Enter stops the measurement. The user will then be asked
to enter the quantity (100 liters). The calculated K-factor is displayed after confimation.