9. ANNEXES.
9.1. PARTICULAR SPECIFICATIONS,
EQUIPMENTS (LV).
Nominal power (kVA)
Nominal power (kW)
Nominal voltage
Input voltage range
Frequency
Total input current distortion
(depending on the quality of input mains)
Input limit for Peak Shaving
Power factor
III/III (with common input)
III/III-B (rectifier input)
III/III-B (bypass input)
(L) I/I (with common input)
(L) I/I-B (rectifier input)
Rated conditional short-
circuit current -Icc- (kA)
(L) I/I-B (bypass input)
(M) I/III-B (rectifier input)
(M) I/III-B (bypass input)
(N) III/I-B (rectifier input)
(N) III/I-B (bypass input)
Output nominal voltage
Output power factor
Accuracy
Output frequency
Maximum slew rate
Output wave shape
Total output voltage harmonic distortion
Phase shifting
Dynamic response time
Permissible overload
(7)
Permissible crest factor
Permissible power factor
Unbalanced output voltage (100 % unbalanced load)
Current limit
Efficiency on battery mode (100% linear load) (%)
Type
Bypass line
Nominal voltage
Voltage range
Voltage hysteresis
Frequency
Frequency range
Frequency hysteresis
Activation criteria
Permissible overload
Transference to bypass
Re-transference
Static bypass for Peak Shaving
150
5
7.5
10
15
Depending on the input/output setting and power supply voltage (See chart 9)
INPUT
Single phase 115V, 120V, 127V or 133V
Three phase 3x200V, 3x208V, 3x220V or 3x230V (4 wires: 3 phases+ N)
50 / 60 Hz ±5 Hz ((selectable among 0.5 - 1 - 2 or 5 Hz)
100 % load: THD-i < 1.5 %
100 % load: THD-i < 1.0 %
50 % load: THD-i < 2.5 %
50 % load: THD-i < 2.0 %
10 % load: THD-i < 6.0 %
10 % load: THD-i < 5.0 %
Configurable between 10%~100% of the power required for the output load
6
6
6
6
6
6
6
6
6
6
INVERTER
Single phase 115V, 120V, 127V or 133V
Three phase 3x200V, 3x208V, 3x220V or 3x230V (4 wires: 3 phases + N)
0.9 for three phase/three phase setting and 0.8 for L, M, N or AUTO settings
Static: ±1 %. Dynamic: ±2 % (step loads 100-0-100 %)
50 / 60 Hz synchronised ±5 Hz. Free running±0.05 %
From 1 to 10 Hz/s (programmable)
Linear load: THD-v < 0.5 %. Ref. non-linear load (EN-62040-3): THD-v < 1.5 %
120 ±1º (balanced load). 120 ±2º (unbalanced load of 100 % )
10 ms. till 98 % of the static value
125 % for 10 min., >125.. 135 % for 5 min., >135.. 150 % for 1 min., > 150 % for 20 ms.
3.4 to 1
High overload, short-circuit: RMS voltage limit. High current crest factor: Peak voltage limit
94.3
95.3
95.6
95.8
STATIC BYPASS
Common. Separate as an option (B)
Single phase 115V, 120V, 127V or 133V
Three phase 3x200V, 3x208V, 3x220V or 3x230V (4 wires: 3 phases + N)
Preset +12 % (adjustable between +20... +5%) / –15% (adjustable between –25... –5%
±2 % as regards the bypass voltage range. In a standard equipment is +10 /–13%
±5 Hz (selectable between 0.5 - 1.0 - 2 and 5.0 Hz)
1 Hz as regards the frequency range (selectable among 0.2 - 0.5 - 1.0 and 2.0 Hz)
Immediately, for overloads over 150 %
Automatic after alarm cancelling
Configurable by user its possible activation
20
30
40
50
+15% / –20% (configurable)
100 % load: THD-i < 1.5 %
50 % load: THD-i < 2.0 %
10 % load: THD-i < 6.0 %
1.0 from 10% load
10
10
10
10
-
-
10
-
-
10
-
-
10
-
-
10
-
-
10
-
-
10
-
-
Sinewave
3.2 to 1
2.8 to 1
3.2 to 1
0.7 leading to 0.7 lagging
< 1 %
96.4
96.5
Solid state(SCR)
50 / 60 Hz
Controlled by microprocessor
400 % for 10 s
60
80
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 to 1
96.4
96.8
96.9
-
SALICRU