SLC CUBE 3+
11:19:35 11/09/2013
screen 0.0
() ()
CONTROL & STATUS
OF THE UNIT
screen 1.0
() ()
MEASURES
screen 2.0
() ()
PARAMETERS
screen 3.0
() ()
ALARMS
screen 4.0
() ()
DATA LOGGER
screen 5.0
() ()
CONFIGURATION
Password: *****
(*1)
screen 6.0
() ()
RATED VALUES
screen 7.0
Fig. 48. Classification of the menus and submenus displayed in the
LCD panel.
7.3. SCREEN DESCRIPTION.
7.3.1. Main level (screen menu 0.0). See Fig 44.
Screen 0.0:
Main presentation
a.
SLC CUBE 3+
11:19:35 11/09/2013
screen 0.0
DSP Ver.: ver. 3.2 a
Uc Ver.: ver. 2.4 b
screen 0.2
When pressing key (ESC) from any screen of any submenu, it is
gone back to main screen (Screen 0.0).
Fig. 49. Screen 0.0 «Start» and its submenus.
138
Firmware versions, serial
()
number, configurations, ...
()
Unit Start-up, battery test
()
command, ...
()
Measurements: voltages, cur-
()
rents, power, temperatures,
()
...
Basic parameters program-
()
mation: date, time, language,
()
communications, ...
Active alarms.
()
()
Last 100 alarms & events oc-
()
curred can be displayed in this
()
submenu, and also the status
of the unit at that moment.
Configuration of the unit,
measures calibration, internal
()
parameters adjustment, ...
()
For Technichal Service
only (password required).
At user level, inspection of
some rated values like input &
()
bypass voltage, input & bypass
()
margins, DC voltage, output
current, charging battery cur-
rent and battery probe..
screen, with time and date indication.
()
UPS:
()
CFG:
screen 0.1
()
UPS Serial Number
()
09 A-321899
screen 0.3
Screen for parallel equipments: the first row of the
b.
screen changes between "SLC CUBE3+ PS" and "Paral.--
Out.SW=---", and where:
Paral. ---, corresponds to the address of each UPS
ˆ
with three characters.
Out.SW ---, corresponds to the position of the output
ˆ
switch of the UPS and/or switchgear panel board,
with two status ON and OFF (the auxiliary contact
of the output switch in the output panel board has
to be connected according to the instructions of sec-
tion 5.2.9.2.).
Screen 0.1: UPS Status ("UPS:", 1
(''CFG:", 2
row). In the first row, there are two fields, first one
nd
shows the general state of the converters, and second one
shows the origin of the voltage at the output. These two fields
are separated by a " , ":
Possible states of the converters:
ˆ
«Shutdown» Rectifier and Inverter stopped or blocked.
«Start up» UPS converters (rectifier and inverter) are
started up, but not ready yet.
«Normal» UPS is running in normal mode: mains pre-
sent, rectifier running, output on inverter, loads are
protected.
«Discharge» Mains failure. UPS running on back-up
mode (rectifier shutdown, inverter running).
Origin of the output:
ˆ
«OFF» No voltage supplied at the output (either EPO
pressed, or severe problem in the equipment).
«Invert» Inverter voltage is supplied at the output.
Loads are protected.
«Bypass» Bypass voltage is supplied at the output.
Either the equipment is manually shutdown, or over-
loaded, or other possible problem in the inverter.
In the second row, there is the hierarchy of the UPS as regards
to the rest of the system, which is dynamic depending on the
status of the rest of the equipments. For «Single» equipment,
the LCD will display the message «CFG: Single»
Equipment hierarchy (parallel systems):
ˆ
«Paral. Mst. Byp» bypass Master of the parallel
system. By default, the first UPS starting up the in-
verter according to the established procedure.
«Paral. Slv. By.Rsv» reserved bypass Slave. Initially
corresponds to the equipment with the highest ad-
dress excepting the one from «bypass Master». In
case of failure of the Master, it will take its functions.
()
«Paral. Slv. Byp» bypass Slave of the parallel system
()
(systems with more than two equipments only). It will
become as «reserved bypass Slave», when it practise
as «bypass Master». In systems with more than three
equipments in parallel, the hierarchy of «reserved by-
pass Slave» will be taken by the one with the highest
address among the «bypass Slave».
«Paral. Mst. Volt» voltage Master of the parallel
system. By default, the first UPS on normal operating
(inverter in operation), that the output switch (Q2) is
turned «On».
row) and configuration